Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 8.6.1.4.1 - Provide code compliant maintenance records. 6/1/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing A category 5 test is due on the overspeed valve in 2025.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 9/14/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be posted in the elevator machine room. 6/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans, shall not exceed 5 gal before removal, shall be covered, and shall not be permitted to overflow. Note: Per the State of Missouri AHJ: "The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals", and "machine rooms cannot be used as containment areas.”
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits x Clean the elevator pit. 6/18/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide code compliant maintenance records. 6/1/2020
A17.1-1996 : Elevators 3.19 - Guide rails fastening and equipment 1001.2(c)(25) Replace the worn car roller guides. 6/1/2020
A17.1-1996 : Elevators 3.19 - Guide rails fastening and equipment 1001.2(c)(25) Replace the worn roller guides. 6/1/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The auxiliary power lowering operation shall be functional. 10/9/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency alarm bell shall be operational on regular and auxiliary power. 4/17/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The in car emergency light shall be operational. 4/17/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 5/7/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 The pit ladder shall extend no less than 30" above the pit access door sill. 9/13/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit light switch shall be accessible from the pit access door. 9/13/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit light switch shall be accessible from the pit access door.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit light switch shall be accessible from the pit access door.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit shall be kept clean. 6/1/2020