Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Provide feeder location on main line and 110v disconnect.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide maintenance control program.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 3.18 Pit bucket was overflowing. Replace packing.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Provide feeder location on the main line disconnect.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) x Car had difficulty going to’M’ floor, then clearing and resetting on Phase II operations. Repair as needed. 6/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide existing phone to work correctly. 6/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x Provide existing battery backup lowering unit to work properly. 6/26/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods x The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. Reinspection required. 6/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide existing battery backup lowering unit to work. 8/29/2024