Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Yes No CAR DOOR RESTRICTOR SHALL WORK AT ALL POINTS IN THE HOISTWAY WHEN THE CAR IS MORE THAN 18" ABOVE OR BELOW LANDING SILL. Multiple brackets are missing
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Machine room door shall be self-closing and self-locking, door will not latch unless forced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No Fire Service must be tested and properly documented monthly on Log Sheet located in the MCP. Log is blank.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No The in car emergency lighting shall be operational. 10/6/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No The in car emergency alarm bell shall be operational. 10/6/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No 3.26.10 - The auxiliary power lowering operation shall be functional. 6/2/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/20/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No 3.26.10 - The auxiliary power lowering operation shall be functional. 6/20/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current State Operating Permit shall be obtained and displayed in the Equipment Room. 6/4/2026