Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.8 - Top emergency exit 8.11.2.1.3(l) No No Top emergency exit shall be properly mounted to the cartop with either hinges or a chain tethered to the cartop to prevent accidental dropping of the hatch
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Where spring buffers, elastomeric buffers, or solid bumpers are used, the bottom runby shall be not less than 150 mm (6 in.),
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 5/27/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The car safeties shall be tested with a full load. 7/29/2021
MO Minimum : Elevators (H) - Machine Rooms (H)3 No No The machine room floor shall cover the entire area of the machine room. Provide a cover or guard the unused machine room access opening. 5/27/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No The machine room lighting shall be not less than 10 foot-candles at the floor. 5/27/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Provide hoist rope data tag. 5/27/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Determine and correct cause of car not running while on car top inspection. 7/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The in car emergency telephone shall be operational. 7/29/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 5/27/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current State Operating Permit shall be obtained and displayed in the Equipment Room 6/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No Fire Service must be tested and properly documented monthly on Log Sheet located in the machine room. No logs present in Machine Room