Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Determine and correct cause of car not running while on car top inspection. 7/29/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The car safeties shall be tested with a full load. 7/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency telephone shall be operational. 7/29/2021
MO Minimum : Elevators (H) - Machine Rooms (H)3 The machine room floor shall cover the entire area of the machine room. Provide a cover or guard the unused machine room access opening.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting shall be not less than 10 foot-candles at the floor.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide hoist rope data tag.