MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
5/27/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current State Operating Permit shall be obtained and displayed in the Equipment Room
|
6/4/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
5/27/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
Yes
|
No
|
Determine and correct cause of car not running while on car top inspection.
|
7/29/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
No
|
No
|
Fire Service must be tested and properly documented monthly on Log Sheet located in the machine room. No logs present in Machine Room
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
Provide hoist rope data tag.
|
5/27/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The car safeties shall be tested with a full load.
|
7/29/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
The in car emergency telephone shall be operational.
|
7/29/2021
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)3
|
No
|
No
|
The machine room floor shall cover the entire area of the machine room. Provide a cover or guard the unused machine room access opening.
|
5/27/2026
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
No
|
No
|
The machine room lighting shall be not less than 10 foot-candles at the floor.
|
5/27/2026
|
|
A17.1-2016 : Elevators
|
3.8 - Top emergency exit
|
8.11.2.1.3(l)
|
No
|
No
|
Top emergency exit shall be properly mounted to the cartop with either hinges or a chain tethered to the cartop to prevent accidental dropping of the hatch
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
Where spring buffers, elastomeric buffers, or solid bumpers are used, the bottom runby shall be not less than 150 mm (6 in.),
|
|