Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide maintenance control program and updated monthly elevator fire log. 3/12/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) No No Provide code compliant machine room lighting (19fc) 3/12/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 8.11.2.1.2(k) No No Provide feeder location for main line and 110v disconnect. 3/12/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Provide testing of existing emergency battery back-up unit. Written testing procedures are required for maintenance control program. 9/1/2020
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not working, phone line not working. Re-inspection required 6/8/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Emergency light shall be operational. 3/27/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm bell shall be operational. 3/27/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No This elevator is equipped with an overspeed valve and category 5 testing is due. 3/27/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 Yes No Doors do not automatically open when battery power is activated. Door operators must be manually reset any time power is lost. 1/22/2026
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3 Yes Yes The opening of doors shall be on continuous pressure. When pressure is released, doors fail to return to the closed position. 1/22/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.1.4(l) Yes Yes Fireman's stop switch shall work. Reinspect only. Unit was not red-tagged. 11/1/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Repair inoperative emergency phone. 7/29/2019