A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
|
Clean oil from elevator pit.
|
11/25/2019
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Clean elevator pit.
|
4/29/2020
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Written maintenance control program shall be kept on site for each elevator.
|
11/28/2022
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV needs to be tested in 90 days or less
|
5/6/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Post Phase I instructions, near the f/f switch in the lobby.
|
12/5/2023
|
A17.1-1996 : Elevators
|
1.13 - Emergency exit
|
204.1e
|
x
|
|
Drop ceiling does not allow access to emergency exit. Take corrective action as needed.
|
1/13/2025
|
A17.1-2016 : Elevators
|
1.13 - Emergency exit
|
2.14.1.5
|
x
|
|
Drop ceiling does not allow access to emergency exit. Take corrective action as needed. Note: Car top emergency exit panel opens up to ceiling panel release latch. However, the whole back ceiling panel drops down for emergency exit, and the other ceiling panel release latch on the other end is under the car top with no access to it. Need to correct problem or apply for variance.
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
All electrical covers shall be installed at completion of second elevator.
|
8/21/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
All smokes and heat detectors must be tested when second car is finished.
|
8/21/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Scavenger pump must be removed, cannot log amount of oil loss from packing gland
|
11/28/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Elevator pit needs to have oil removed
|
11/28/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be on display in the elevator machine room
|
11/28/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Need to clean pit
|
11/28/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light is not working
|
11/28/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be on display in the machine room
|
11/28/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Scavenger pumps that do not record the amount of oil returned to the hydraulic tank can not be installed. Either install recordable scavenger pump or limit the amount of oil stored in the pit to 5 gallons.
|
11/28/2022
|