Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Replace or reinforce sump hole cover in pit 7/2/2019
MO Minimum : Elevators (I) - Pits (I)1 Water and oil shall not be allowed to accumulate on pit floors. 8/30/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational on auxiliary power. 8/15/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 8/15/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The displayed certificate is expired. A current MO State operating certificate shall be obtained and displayed in the machine room. 9/18/2023
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. Remove water from the pit. 9/18/2023