MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)2
|
x
|
|
The directional limits in both directions shall activate before the final limits.
|
8/12/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
10/23/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
|
6/28/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
6/28/2022
|
conversion
|
conversion
|
conversion - red tag
|
x
|
x
|
Repair Fire Service
|
1/31/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Repair phone in car
|
1/31/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
1) The main floor landing has a smoke which doesn't recall elevator to alternate landing. The building is in the process of signing a contract for a new controller. This alteration will correct the violation when it is performed. I am giving the 30 days to get a signed contract which will address this violation when completed.
|
5/31/2018
|
conversion
|
conversion
|
n/a
|
|
|
Post current State Certificate in Machine Room
|
6/28/2022
|