A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Pit must be kept free of water (currently 1" standing water) 8.6.4.7.4
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
alarmlemergency light needs battery
|
1/6/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
8.6.5.5.1 & 8.6.12.3.7.2 packing needs replaced
|
2/13/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Pit scavenger pump will be removed or routed to a measurable container.
|
3/17/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept dry, repair water leak
|
3/17/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Water in Pit
|
1/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
No records
|
1/31/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Clean Machine Room
|
12/20/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone failed.
|
4/23/2024
|