A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
8.11.3.1.3(b)
|
|
|
The car top inspection light/fixture did not operate. Repair light/fixture for proper operation and illumination for maintenance/emergency personnel.
|
|
A17.1-2016 : Elevators
|
1.14 - Ventilation
|
8.11.3.1.1(n)
|
|
|
The ventilation fan in the elevator car has been removed and shall be reinstalled for ventilation/passenger safety.
|
|
conversion
|
conversion
|
n/a
|
|
|
Provide correct Phase 1 fire service instructions in the lobby.
|
9/17/2020
|
conversion
|
conversion
|
n/a
|
|
|
The fire extinguisher in the machine room is expired.
|
9/17/2020
|
conversion
|
conversion
|
n/a
|
|
|
Remove all non-elevator related equipment from the machine room.
|
9/17/2020
|
conversion
|
conversion
|
n/a
|
|
|
In car ventilation fan is broken.
|
9/17/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher in the machine room is expired and shall be serviced or replaced with a current extinguisher.
|
9/17/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean. Clean the pit.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
The machine room shall be kept clean. Items and materials not related to the operation or maintenance of the elevator shall not be stored in the machine room.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
The car top shall be cleaned.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
x
|
|
The visual fire service indicator in the elevator car shall be illuminated when either phase of fire service is activated.
|
4/13/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
The elevator car top shall be cleaned of dust and debris.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required.
|
3/22/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in dust and debris. The pit shall be cleaned.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: Phase II did not initiate when the fireman's emergency service key was turned to the “ON” position. Reinspection in 14 days required.
|
3/22/2023
|