Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 9/19/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Clean debris from elevator pit. 9/19/2023
A17.1-1996 : Elevators 3.33 - Compensating ropes and chains 202.4 x Compensating chain support is broken on one side, needs replaced. Re-inspection required 11/13/2023
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 107.1b x Counterweight runby is less than 6". Hoist ropes need to be shortened. Re-inspection required 6/17/2024
A17.1-1996 : Elevators 1.12 - Car enclosure 1001.2(a)(12) Repair handrail inside of elevator cab. 9/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Repair or replace bent rod on car buffer
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) Repair relating cable on third floor 3.17.1 (3) 9/19/2023