MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
The car top shall be kept clean. Clean the car top.
|
10/17/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
10/17/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
Need to provide cover on handy box containing 110V wiring on side of controller
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Elevator will not return to Phase I and return to main landing. Re-inspection required in 20 days
|
5/5/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Elevator will not return back to Phase 1 fire service from Phase 2 fire service.
|
9/3/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The auto return feature after coming off Phase 2 fire service does not work and shall be repaired. Note: Both Phases of fire service operate correctly.
|
11/5/2021
|