Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/17/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x Elevator will not return back to Phase 1 fire service from Phase 2 fire service. 9/3/2020
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Elevator will not return to Phase I and return to main landing. Re-inspection required in 20 days 5/5/2023
MO Minimum : Elevators (H) - Machine Rooms (H)8 Need to provide cover on handy box containing 110V wiring on side of controller
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The auto return feature after coming off Phase 2 fire service does not work and shall be repaired. Note: Both Phases of fire service operate correctly. 11/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars The car top shall be kept clean. Clean the car top. 10/17/2022