Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/17/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Cab emergency alarm bell does not work and shall be repaired and tested. 5/2/2019
conversion conversion n/a No No Emergency light shall work. 5/2/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired, replace or have serviced 10/28/2025
conversion conversion n/a No No Machine room shall not be used for storage of non-elevator related items. 5/2/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light shall work. 5/2/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Yes No Post current State Elevator Certificate. 10/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation No No Provide updated MCP. 10/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Yes No The car door restrictor shall be operational. 1/7/2021