Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency bell shall be operational. 10/20/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The in car emergency lighting shall be operational. 10/20/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) x x The car stop switch shall be bypassed on Phase 1 fire recall. 10/20/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit shall be kept clean.
A17.1-1996 : Elevators 1.14 - Ventilation 1001.2(a)(14) A cab ventilation fan shall be operational and shall be properly guarded.
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) The machine room door shall be self-closing and self-locking.
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide existing phone to work. 7/22/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate x Post current State Elevator Certificate.
A17.1-1996 : Elevators 3.17 - Door and gate equipment 110 Car top door operator missing belt. Unit requires 3 belts, 1 missing.
A17.1-1996 : Elevators 3.17 - Door and gate equipment 110 Hoistway doors (bottom door guides) -check for proper installation.
conversion conversion n/a The fire extinguisher in the machine room is expired. 4/30/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors Car floor tiles are worn and breaking, replace as needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation x Provide updated MCP.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door is to be self locking.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit x Clean the pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Car top door operator missing belt (1), provide.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Hoistway doors on 2nd floor, turn down tabs (fire stop/wear indicator) on bottom door guides (2).one on fast door, one on the slow door.