A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5.1 Examination and Maintenance
|
Yes
|
Yes
|
Upon re-inspection, found control valve had been replaced without alteration permit being issued. Elevator still dropped 1 3/4" during three 15 minute standing tests with shut off valve closed. Oil level in tank remained unchanged each time. Left unit Red-tagged. Re-inspection required
|
|
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5 Gland Packing and Seals
|
Yes
|
No
|
Determine where the unit is leaking, the car settled 4" in 15 minutes with no signs of leaking in the elevator pit or machine room. The shut off valve in the machine room was closed. Red-tagged, Re-inspection required.
|
|
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
Yes
|
No
|
The in car stop switch has a broken mounting bezel. The stop switch shall be repaired.
|
6/21/2019
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
In car emergency telephone shall work.
|
9/2/2020
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
Yes
|
No
|
The relief pressure shall be tested.
|
9/2/2020
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone does not work. Re-inspection required
|
11/3/2023
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone shall be made operable
|
5/23/2024
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Need copy of current state operating certificate in machine room.
|
6/4/2026
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Machine room door shall be self-locking.
|
6/4/2026
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
No
|
No
|
The door closing force shall be tested.
|
6/4/2026
|
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5 Gland Packing and Seals
|
Yes
|
Yes
|
Determine where the unit is leaking, the car settled 4" in 15 minutes with no signs of leaking in the elevator pit or machine room. The shut off valve in the machine room was closed. Red-tagged, Re-inspection required.
|
8/14/2026
|