Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No Need copy of current state operating certificate in machine room. 6/4/2026
conversion conversion n/a No No Machine room door shall be self-locking. 6/4/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 No No The door closing force shall be tested. 6/4/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. Re-inspection required 11/3/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall be made operable 5/23/2024
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5 Gland Packing and Seals Yes Yes Determine where the unit is leaking, the car settled 4" in 15 minutes with no signs of leaking in the elevator pit or machine room. The shut off valve in the machine room was closed. Red-tagged, Re-inspection required. 8/14/2026
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.1 Examination and Maintenance Yes Yes Upon re-inspection, found control valve had been replaced without alteration permit being issued. Elevator still dropped 1 3/4" during three 15 minute standing tests with shut off valve closed. Oil level in tank remained unchanged each time. Left unit Red-tagged. Re-inspection required
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5 Gland Packing and Seals Yes No Determine where the unit is leaking, the car settled 4" in 15 minutes with no signs of leaking in the elevator pit or machine room. The shut off valve in the machine room was closed. Red-tagged, Re-inspection required.
MO Minimum : Elevators (F) - Electrical Switches (F)1 Yes No The in car stop switch has a broken mounting bezel. The stop switch shall be repaired. 6/21/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No In car emergency telephone shall work. 9/2/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The relief pressure shall be tested. 9/2/2020