Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.10 replacement of Hydraulic jack,Plunger,Cylinder,Tanks,and Anticreep Leveling Device Yes Yes UNIT FAILED SIT TEST. THE JACK HAS A HOLE IN IT UNDER GROUND
A17.1-2016 : Elevators 2.6 - Ventilation 8.10.2.2.2(k) Yes No HVAC mini-split indoor unit installed over the top of hydraulic pumping unit in machine room. 4/7/2025