Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light in the cab does not work 4/9/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency light not working. 11/20/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency alarm bell not working. 11/20/2019
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm bell does not work on 110v emergency power or normal power 4/9/2024
A17.1-1996 : Elevators 1.7 - Car door or gate 1001.2(a)(7) x Adjust car door to cab clearance to 3/8 max - currently in excess of 1/2 inch. 9/28/2020
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) Machine room needs to be locked at all times. 10/22/2019
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Annual tag shows expired. 11/30/2022
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Provide current year tested fire extinguisher in the elevator machine room.
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) Replace missing door gibbs on 5th floor and missing fire tab on 3rd floor. 9/28/2020
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) Top level door is missing two door gibs. 10/22/2019
A17.1-1996 : Elevators 3.17 - Door and gate equipment 210.1e Gate switch exceeds minimum measurement for center opening doors. Reinspect. 10/22/2019
A17.1-1996 : Elevators 3.2 - Car top light and outlet 204.7 Provide car top light to work.
A17.1-1996 : Elevators 3.8 - Top emergency exit 204.1e Provide means to secure car top exit.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) There needs to be a working lit in the pit. 10/22/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Provide existing pit light to work.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Provide,on Phase II operations, call cancel feature to work.
conversion conversion n/a Post Mo Stae certificate in machine room 10/22/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 10/22/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 10/22/2019