A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light not working.
|
11/20/2019
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm bell not working.
|
11/20/2019
|
A17.1-1996 : Elevators
|
1.7 - Car door or gate
|
1001.2(a)(7)
|
|
x
|
Adjust car door to cab clearance to 3/8 max - currently in excess of 1/2 inch.
|
9/28/2020
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
|
|
Machine room needs to be locked at all times.
|
10/22/2019
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
Top level door is missing two door gibs.
|
10/22/2019
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
Replace missing door gibbs on 5th floor and missing fire tab on 3rd floor.
|
9/28/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
|
Provide,on Phase II operations, call cancel feature to work.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Provide existing pit light to work.
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Provide current year tested fire extinguisher in the elevator machine room.
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Annual tag shows expired.
|
11/30/2022
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
There needs to be a working lit in the pit.
|
10/22/2019
|
A17.1-1996 : Elevators
|
3.8 - Top emergency exit
|
204.1e
|
|
|
Provide means to secure car top exit.
|
|
A17.1-1996 : Elevators
|
3.2 - Car top light and outlet
|
204.7
|
|
|
Provide car top light to work.
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light in the cab does not work
|
4/9/2024
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
210.1e
|
|
|
Gate switch exceeds minimum measurement for center opening doors. Reinspect.
|
10/22/2019
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
10/22/2019
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
10/22/2019
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell does not work on 110v emergency power or normal power
|
4/9/2024
|
conversion
|
conversion
|
n/a
|
|
|
Post Mo Stae certificate in machine room
|
10/22/2019
|