Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 Cab shall be full enclosed. There is a 7x6 hole in the left side of the transom.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 Cab shall be full enclosed. There is a 7x6 hole in the left side of the transom. (Please note that this violation will be corrected when the ventilation fan in the car is repaired)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures not on site for emergency personnel.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures not on site for emergency personnel.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self locking.
A17.1-2016 : Elevators 1.14 - Ventilation 8.11.3.1.1(n) The ventilation fan in the car is inoperable. The fan has been disassembled and shall be repaired as designed.
A17.1-2016 : Elevators 2.37 - Pressure Switch 8.11.3.1.2(y) This elevator does not have a low pressure switch installed in the hydraulic line. The low pressure switch is required for elevators that have the hydraulic jack heads above the hydraulic pump motor. This is a required safety device that should have been installed when the elevator was constructed in 1988. The authority having jurisdiction (St. Louis County) had adopted A17.1 1981 at the time of installation which is addressed in section 306.14
MO Minimum : Elevators (S) - Fire Service (S)1 x x Elevator not equipped with fire recall, but it has a Phase II switch. Switch shall be removed and hole blanked out or full fire recall installed. Did not red tag, given until May 13 2020 to repair. 3/30/2021