Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Clean the elevator pit of debris. 6/26/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Fire service key switch lettering is missing. 6/26/2024
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) Provide car number to be visible inside car. 6/26/2024
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) Provide all floor numbering to be the same concerning main/2nd floor. COP, PI, braille, and hoistway door. 6/26/2024
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The restrictor is not functioning properly, take corrective action. The restrictor shall work in the absence of main power. 3/7/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone did not work properly. The operator was not able to provide the location. 3/7/2024
A17.1-1996 : Elevators 1.7 - Car door or gate 112.2a Repair car door restrictor 3/26/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 3/7/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service Phase 1 & 2 shall be tested. 3/7/2024
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d The machine room or enclosure shall have a self-closing and self-locking door and shall be operable from the interior space without use of a key. 6/26/2024
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. 6/26/2024
A17.1-1996 : Elevators 2.14 - Code data plate 215 Install a code date plate. It shall read MO Min/A17.1-1996. 6/26/2024
A17.1-1996 : Elevators 2.27 - Rope fastenings 212 Wedge rope socket is anchored incorrectly. When the steel wire rope has been seated in the wedge socket by the load of the rope, the wedge shall be visible, and at least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. 6/26/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 6/26/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) The car top is dirty. 6/26/2024
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h The fire extinguisher is expired. 6/26/2024
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 There is a plastic pipe between floors M and G2. No pipes conveying liquids, gases, or vapors shall be located in a hoistway; remove pipe. This violation was written up in 2013. 6/26/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 A permanent lighting fixture shall be provided in all pits to provide an illumination of not less than five (5) foot-candles at the pit floor. 6/26/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 A pit ladder shall be installed for this pit. The ladder shall extend not less than 30" above the sill of the access floor. Ladder shall be made of non-combustible material. The ladder that is installed for this pit is unsafe and does not meet the above criteria. 6/26/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Mid way up pit wall, sump line has separated. Repair or replace as needed. 6/26/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 3/26/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current state certificate shall be posted in the machine room in a noncombustible frame with a clear protective vision plate over it. 6/26/2024