MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
|
|
Clean the elevator pit of debris.
|
6/26/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Rope tags for the hoisting ropes are missing.
|
6/26/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Fire service key switch lettering is missing.
|
6/26/2024
|
A17.1-1996 : Elevators
|
1.15 - sign and operating device symbols
|
1001.2(a)(15)
|
|
|
Provide all floor numbering to be the same concerning main/2nd floor. COP, PI, braille, and hoistway door.
|
6/26/2024
|
A17.1-1996 : Elevators
|
1.15 - sign and operating device symbols
|
1001.2(a)(15)
|
|
|
Provide car number to be visible on the inside of car.
|
6/26/2024
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
The restrictor is not functioning properly, take corrective action. The restrictor shall work in the absence of main power.
|
3/7/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone did not work properly. The operator was not able to provide the location.
|
3/7/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car emergency bell does not work.
|
4/29/2024
|
A17.1-1996 : Elevators
|
1.7 - Car door or gate
|
112.2a
|
|
|
Repair car door restrictor
|
3/26/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
3/7/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service Phase 1 & 2 shall be tested.
|
3/7/2024
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
The machine room enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without use of a key.
|
6/26/2024
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
210.4
|
|
|
The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
6/26/2024
|
A17.1-1996 : Elevators
|
2.14 - Code data plate
|
215
|
|
|
Install a code data plate. It shall read: MO Min/A17.1-1996.
|
6/26/2024
|
A17.1-1996 : Elevators
|
2.27 - Rope fastenings
|
212
|
|
|
The wire-rope retaining clips shall be properly installed. At least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope (see Figure 2.20.9.5). The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip.
|
6/26/2024
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022)
|
6/26/2024
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2c (Clean Car Tops)
|
|
|
The car top is dirty.
|
6/26/2024
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
The fire extinguisher is expired.
|
6/26/2024
|
A17.1-1996 : Elevators
|
3.3 - Top-of-car operating device
|
1001.2(c)(3)
|
|
|
Replace missing cover on handy box top of car
|
3/26/2019
|
A17.1-1996 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
107
|
x
|
|
The car top handrail is striking the secondary sheave guard when the counterweight compresses the counterweight buffer.
|
3/7/2024
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
A permanent lighting fixture shall be provided in all pits to provide illumination of not less than five (5) foot-candles at the pit floor.
|
6/26/2024
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
A pit ladder shall be installed for this pit. The ladder shall extend not less than 30" above the sill of the access floor. Ladder shall be made of non-combustible material. The ladder that is installed for this pit is unsafe and does not meet code.
|
6/26/2024
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certificate in machine room
|
3/26/2019
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
6/26/2024
|