Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.7 - Car door or gate 112.2a Repair car door restrictor 3/26/2019
A17.1-1996 : Elevators 3.3 - Top-of-car operating device 1001.2(c)(3) Replace missing cover on handy box top of car 3/26/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 3/26/2019
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) Provide all floor numbering to be the same concerning main/2nd floor. COP, PI, braille, and hoistway door. 6/26/2024
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) Provide car number to be visible on the inside of car. 6/26/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 6/26/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/26/2024
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d The machine room enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without use of a key. 6/26/2024
A17.1-1996 : Elevators 2.14 - Code data plate 215 Install a code data plate. It shall read: MO Min/A17.1-1996. 6/26/2024
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. 6/26/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone did not work properly. The operator was not able to provide the location. 3/7/2024
A17.1-1996 : Elevators 2.27 - Rope fastenings 212 The wire-rope retaining clips shall be properly installed. At least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope (see Figure 2.20.9.5). The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. 6/26/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 A permanent lighting fixture shall be provided in all pits to provide illumination of not less than five (5) foot-candles at the pit floor. 6/26/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 A pit ladder shall be installed for this pit. The ladder shall extend not less than 30" above the sill of the access floor. Ladder shall be made of non-combustible material. The ladder that is installed for this pit is unsafe and does not meet code. 6/26/2024
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The restrictor is not functioning properly, take corrective action. The restrictor shall work in the absence of main power. 3/7/2024
A17.1-1996 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 107 x The car top handrail is striking the secondary sheave guard when the counterweight compresses the counterweight buffer. 3/7/2024
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h The fire extinguisher is expired. 6/26/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) The car top is dirty. 6/26/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x In car emergency bell does not work. 4/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Fire service key switch lettering is missing. 6/26/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 3/7/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service Phase 1 & 2 shall be tested. 3/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Clean the elevator pit of debris. 6/26/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Rope tags for the hoisting ropes are missing. 6/26/2024