Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 emergency light and bell failed 1/16/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4 Instructions for Locating Maintenance Records no testing procedures no valve info 7/31/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No current city. Posted
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(c)(5) Need test procedure for overspeed valve
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt. displayed
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt displayed
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) pit lt not working
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) x couldnt test emg power at time of insp
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) x Emg Battery lowering not working 7/8/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x when at a floor with both front an rear doors at that foor both front an rear doors open at the same time. 7/8/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x both car doors open or closed from either set of car buttons at same time at floor with opposed openings 1/19/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) x Battery lowering not working 1/19/2024