Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Elevator Equipment room door knob needs to be replaced with self locking door knob 8/15/2023
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) No No Door knob to machine space must be self locking 8/15/2023
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No Fire extinguisher in elevator equipment room overdue inspection 8/15/2023
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 1001.2(b)(8) No No Need cover over receptacle in elevator equipment room. 8/15/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No TKE needs to supply on-site maintenance records per code requirements 8/15/2023
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space No No Non-elevator stuff can not be stored in Elevator Equipment Room 8/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Pick-up rollers need to be replaced on Floor 2 and 3 8/2/2021
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No LIGHT MUST BE OPERATIONAL
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No PHONE MUST CALL A WORKING NUMBER