MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Pick-up rollers need to be replaced on Floor 2 and 3
|
8/2/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Elevator Equipment room door knob needs to be replaced with self locking door knob
|
8/15/2023
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
|
|
Door knob to machine space must be self locking
|
8/15/2023
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Fire extinguisher in elevator equipment room overdue inspection
|
8/15/2023
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
1001.2(b)(8)
|
|
|
Need cover over receptacle in elevator equipment room.
|
8/15/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
TKE needs to supply on-site maintenance records per code requirements
|
8/15/2023
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Room and Machinery Space
|
|
|
Non-elevator stuff can not be stored in Elevator Equipment Room
|
8/15/2023
|