Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/1/2022
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Counterweight safety slide was 9" short of the minimum requirement. Unit Red Tagged 1/22/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x Elevator would not respond to Phase 1 key switch. - Red Tag 9/4/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power shall be tested. 8/7/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power shall be tested. 8/15/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service and emergency power operation shall be tested. 12/4/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service shall be tested. 8/7/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service shall be tested. 8/15/2020
MO Minimum : Elevators (D) - Brakes (D)2 x x The machine brake would not hold empty car. - Unit Red Tagged 8/7/2020