Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/1/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x x Door open button failed to open doors on fire service phase 2 operation. - Elevator Red Tagged.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x The counterweight buffer shall be of equivalent design to the original counterweight buffer. The counterweight buffer shall be replaced. - Unit Red Tagged 9/4/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service and emergency power shall be tested. 12/4/2024