MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The overhead machine room lighting shall be operational. 4/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Provide code compliant runby.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service and emergency power shall be tested.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The overhead sheaves are excessively worn and causing excessive wear to the hoist ropes. Replacement of the sheaves and ropes are required. 7/29/2020