Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The overhead sheaves are excessively worn and causing excessive wear to the hoist ropes. Replacement of the sheaves and ropes are required. 7/29/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No The overhead machine room lighting shall be operational. 4/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) Yes No Provide code compliant runby. 6/16/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Fire service and emergency power shall be tested. 6/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/1/2022