Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired. Replace or have serviced
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Need to test & tag fire extinguisher in machine room
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light does not work on 110v emergency power 10/7/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency bell does not work on 110v emergency power 10/7/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV not sealed. Perform OSV test on or before next annual inspection. 4/10/2023
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Need to make machine room door self locking
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site for each elevator. 4/10/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room