Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/19/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/19/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Fire service bezel has faded and shall be replaced. 10/28/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x The auxiliary power lowering shall be fuctional.
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x The battery lowering device shall be operational. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10. 8/19/2021
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 1001.2(b)(11) The disconnect in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. 8/19/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 8/19/2021