Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x The emergency bell is not working. 7/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency lights are not working on battery backup. 7/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 6/1/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans, shall not exceed 5 gal before removal, shall be covered, and shall not be permitted to overflow. Note: Per the State of Missouri AHJ: "The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals", and "machine rooms cannot be used as containment areas". 6/1/2021
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and free of oil. 6/17/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 7/13/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. 9/18/2024