MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Replace the light tubes in the car ceiling.
|
8/6/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Replace the missing light tubes in the car ceiling.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Replace the worn door gibbs the door is draging
|
10/27/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Replace the missing braile plates floor 1 and 2
|
8/6/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Replace the compensation rope due to excessive damage to the covering in many places.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Replace the burnt out light tubes in the machine room.
|
8/6/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
replace the burnt out light tubes in the machine room ceiling , you are to provide a minimum of 20 ftc at the machine room floor.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)2
|
|
|
Repair or replace both of the buffers due to excessive rust damage due to standing water in the pit.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)3
|
|
|
Repair the damaged comp chain jacket, as it has been snagged and damaged.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Replace the burnt out pit light.
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Replace the govoner rope due to excessive rouging and broken wire lays near the bottom .
|
5/31/2024
|
MO Minimum : Elevators
|
(N) - Guide Rails
|
(N)2
|
|
|
Repair or replace the lower sections of both guide rails due to excessive rusting from standing water in the pit.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair the emergency phone as there is no dial tone.
|
8/6/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.20 - Governor rope
|
8.11.2.1.3(z)
|
|
|
Replace the badly roughed govenor rope
|
7/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.20 - Governor rope
|
8.11.2.1.3(z)
|
|
|
Replace the very badly rouged governor rope due to excessive rouging.
|
7/14/2022
|
conversion
|
conversion
|
n/a
|
|
|
Car door exceeds 30 pounds of torque- Reduce to under 30 pounds
|
6/4/2019
|
conversion
|
conversion
|
n/a
|
|
|
Replace pit light
|
6/4/2019
|
conversion
|
conversion
|
n/a
|
|
|
Emergency light and bell doesn't work .
|
6/4/2019
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Obtain and display a current state operating certificate in the machine room
|
8/6/2020
|