                        MO Minimum : Elevators
                     | 
                    
                        (B) - Car Enclosure: Passenger
                     | 
                    
                        (B)8 Car Lighting
                     | 
                    
                     | 
                    
                     | 
                    
                        Emergency light does not work. 1.5
                     | 
                    
                        7/2/2020
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (G) - Maintenance, Repair and Replacements
                     | 
                    
                        (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Emergency phone does not work. Re-inspection required
                     | 
                    
                        7/14/2025
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (S) - Fire Service
                     | 
                    
                        (S)1
                     | 
                    
                            x
                     | 
                    
                            x
                     | 
                    
                        Unit failed to override in car stop switch on Phase I recall.  Did not return to main recall upon turning off Phase II.  Red tagged unit.
                     | 
                    
                        7/19/2021
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        11 CSR 40-5.090 Inspection and Testing
                     | 
                    
                        8.6.5.16.5 Over Speed Valve Testing
                     | 
                    
                     | 
                    
                     | 
                    
                        OSV is not sealed. Perform OSV test, tag, and seal upon completion within 90 days.
                     | 
                    
                        8/2/2021
                     | 
                
                
                    | 
                        A17.1-2016 : Elevators
                     | 
                    
                        5.15.2 Unsealed Overspeed Valve
                     | 
                    
                        8.6.5.16.5 (Re-Inspect)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        OSV is not sealed.  Perform OSV test within 90 days.
                     | 
                    
                        6/3/2022
                     |