Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed. Perform OSV test within 90 days. 6/3/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed. Perform OSV test, tag, and seal upon completion within 90 days. 8/2/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x x Unit failed to override in car stop switch on Phase I recall. Did not return to main recall upon turning off Phase II. Red tagged unit. 7/19/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Emergency light does not work. 1.5 7/2/2020