Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit (oil,pads). 10/15/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency generator testing shall be performed. Re-inspection required 12/19/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency generator testing shall be performed. Re-inspection required
A17.1-2016 : Elevators 2.7 - Fire Extinguisher NFPA 10- 6.1.3.8.3 Installation Height 4" from floor x Fire extinguisher shall be installed appropriately in the machine room.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service testing must be documented monthly 12/19/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service testing must be documented monthly. 10/15/2025
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x HVAC installation shall be completed and operating correctly.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) The OTIS MCP and documentation for 2021, 2022 & 2023 are missing. 10/15/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x The signage for “In Case of Fire Use Stairs” is not located on all landings.. Install signage that conforms to the building code this elevator was installed to meet.