Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Hoist ropes are showing rouge and are undersized, replace ropes within 60 days. Re-inspection required 4/8/2024
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. 3/21/2021
MO Minimum : Elevators (F) - Electrical Switches (F)2 x The final and normal limit switches shall be adjusted to operate for proper run-by of the counterweight and buffer. Reinspection required. 3/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 3/9/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device as failed. Repair for proper operation. Reinspection required. 3/9/2020
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. 2/25/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 2/25/2020
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. 3/8/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 3/8/2019
MO Minimum : Elevators (F) - Electrical Switches (F)9 x Sprinkler heads have been added to the elevator machine room, top of the elevator hoistway, and elevator pit without the required heat detectors to activate the shunt trip disconnect before the application of water. Heat detectors shall be installed within 2’ of each sprinkler head to activate the shunt trip disconnect.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x A17.1 1996 2.11.3b With the addition of sprinklers at the top of the hoistway, smoke detectors are now required and shall be tied into the elevator controller for proper fireman phase I recall operation.
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage There is no signage for Firefighters Operation by the phase I key switches. Obtain the correct signage from the building code addition that this elevator was designed to meet.
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit light fixture failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five (5) foot candles at the pit floor for maintenance and emergency personnel.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x The elevator hoisting ropes are showing a high degree of wear/rouge and shall be replaced. Replace ropes within 60 days of inspection. Alteration permit and reinspection required.