Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 No No The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. 3/8/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 3/8/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 3/9/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device as failed. Repair for proper operation. Reinspection required. 3/9/2020
MO Minimum : Elevators (I) - Pits (I)1 No No The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. 2/25/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 2/25/2020
MO Minimum : Elevators (F) - Electrical Switches (F)2 Yes No The final and normal limit switches shall be adjusted to operate for proper run-by of the counterweight and buffer. Reinspection required. 3/12/2021
MO Minimum : Elevators (I) - Pits (I)1 No No The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. 3/21/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Hoist ropes are showing rouge and are undersized, replace ropes within 60 days. Re-inspection required 4/8/2024
MO Minimum : Elevators (F) - Electrical Switches (F)9 Yes No Sprinkler heads have been added to the elevator machine room, top of the elevator hoistway, and elevator pit without the required heat detectors to activate the shunt trip disconnect before the application of water. Heat detectors shall be installed within 2’ of each sprinkler head to activate the shunt trip disconnect. 10/1/2025
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No A17.1 1996 2.11.3b With the addition of sprinklers at the top of the hoistway, smoke detectors are now required and shall be tied into the elevator controller for proper fireman phase I recall operation. 10/1/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No There is no signage for Firefighters Operation by the phase I key switches. Obtain the correct signage from the building code addition that this elevator was designed to meet. 10/1/2025
MO Minimum : Elevators (I) - Pits (I)1 No No The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. 10/1/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The pit light fixture failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five (5) foot candles at the pit floor for maintenance and emergency personnel. 10/1/2025
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No The elevator hoisting ropes are showing a high degree of wear/rouge and shall be replaced. Replace ropes within 60 days of inspection. Alteration permit and reinspection required. 10/1/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Elevator phone in cab dials out but unsure if someone is answering, cannot confirm connection to operator. Phone shall be monitored by a 24/7 service. Re-inspection required