Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) No No A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. 3/15/2026
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 3/15/2026
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Yes No OSV NOT TESTED AT THIS TIME TO VERIFY OPERATION 3/11/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No reprogram emergency phone, call could not be completed as dialed 4/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No the state operating certificate in the machine room is from 2013, it is to be updated every year with a new copy 3/15/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No monthly fire service test log is to be kept in the machine room 3/15/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Replace the battery for the emergency phone, it will not dial out with the 110 volt power off 7/8/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current copy of the State Operating Certificate in the machine room 3/15/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No Post monthly fire service test log in the machine room 3/15/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Post instructions for viewing on-site the records for the Maintenance Control Program (MCP) 3/15/2026