MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Annual inspection incomplete. Need to test fire service.
|
4/5/2021
|
|
A17.1-1996 : Elevators
|
5.9 - Buffers and emergency terminal speed limiting devices
|
201
|
Yes
|
No
|
Counterweight buffer needs to be repaired.
|
4/5/2021
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
No
|
No
|
Elevator machine room lighting is inadequate, provide at least 19 foot candles of lighting in all areas of machine room
|
4/27/2026
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone is not being answered.
|
9/30/2020
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Phone in elevator cab does not work. Phone line problem.
|
11/29/2023
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
No
|
No
|
Remove all non-elevator equipment stored in elevator machine room.
|
4/27/2026
|
|
A17.1-1996 : Elevators
|
1.12 - Car enclosure
|
204
|
No
|
No
|
Replace missing cab panel.
|
12/13/2021
|
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
Yes
|
No
|
The car door restrictor shall be made operational. Re-inspection required
|
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
No
|
No
|
The ceiling has been removed and there shall be plastic tubes covering the fluorescent bulbs
|
|
|
A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
2.11
|
No
|
No
|
The sill closer at the first floor shall be made operational
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
No
|
No
|
Top right counterweight roller has a worn out bearing, replace roller.
|
4/27/2026
|