Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Annual inspection incomplete - need to test fire service. 4/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Counterweight runby is less than 6". Hoist ropes need to be shortened. Re-inspection required 6/3/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light in car does not work. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light in car does not work. Re-inspection required 6/3/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone is not being answered. 9/30/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Light bulbs in car shall be guarded to protect passengers in event of bulb breakage. Install solid ceiling panels or plastic tubes and endcaps over bulbs.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Light bulbs in car shall be guarded to protect passengers in event of bulb breakage. Need to install solid ceiling panels or plastic tubes and endcaps over bulbs
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lighting in machine room shall provide at least 19 fc illumination at floor in front of controller
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lighting in machine room shall provide at least 19 fc illumination at floor in front of controllers.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work. Phone line problem 11/29/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light shall work
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be cleaned
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove all materials not related to elevators from machine room
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove all materials not related to elevators from machine room
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Remove water from the pit. 12/13/2021
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Repair cab ceiling light fixture, missing ceiling tile. 12/13/2021
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x Repair front door restrictor within 14 days. 9/30/2020
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Unable to place car calls in Phase II fire service operation, needs repair. Re-inspection required 6/3/2024