conversion
|
conversion
|
conversion - reinspect
|
Yes
|
No
|
Repair Door ristrictor
|
5/7/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters' Emergency Operation: Operating Procedures
|
Yes
|
No
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: In phase II the door close operation failed to properly close the car door, repair and reinspection is required within 15 days or the elevator shall be removed from service.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
Yes
|
No
|
This elevator has an overspeed valve device installed and is required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Overspeed valve shall be tested and a reinspection is required.
|
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Door Closing Force is above 30lbs. Lower below 30
|
4/13/2018
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
No
|
No
|
Remove oil from pit floor.
|
7/14/2020
|