Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures Yes No The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: In phase II the door close operation failed to properly close the car door, repair and reinspection is required within 15 days or the elevator shall be removed from service.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Remove oil from pit floor. 7/14/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No This elevator has an overspeed valve device installed and is required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Overspeed valve shall be tested and a reinspection is required.
conversion conversion conversion - reinspect Yes No Repair Door ristrictor 5/7/2019
conversion conversion n/a No No Door Closing Force is above 30lbs. Lower below 30 4/13/2018