Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x FAID testing failed to operate under the requirements of A17.1 2016. Initiating devices shall be repaired and pre-tested prior to reinspection. 8/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 x A numerous amount of fire retaining tabs are missing on each hoistway door. The fire retaining tabs shall be replaced. 8/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 8.11.3.1.2 (o) x Repair and replace control. Valve is leaking excessively. 5/17/2022
conversion conversion conversion - reinspect x Door closing force above 30 lbs on both card doors 5/14/2019
conversion conversion n/a Clean pit of oil and debris 10/13/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair inoperative emergency phone 8/22/2024