MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The Braille floor identification tag is missing on the ground floor door jamb. Reinstall tag for ADA compliance.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The Braille floor identification tag is missing on the ground floor door jamb. Reinstall tag for ADA compliance
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
The hoistway door jamb at the 3rd floor is damaged and is peeling away from the wall. The door jamb shall be repaired to a smooth finish.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The Braille floor identification tag is missing on the ground floor door jamb. Reinstall tag for ADA compliance.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in dust and debris. The pit shall be cleaned.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.11.2.1.1(o)
|
|
|
There are a number of Braille floor indicating/push button tags that are missing on multiple floors and shall be reinstalled for proper floor identification.
|
7/30/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7
|
|
|
The car top inspection light/fixture did not operate. Repair light/fixture for proper operation and illumination for maintenance/emergency personnel.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)
|
|
|
Replace suspension ropes due to reduced diameter. Will require a permit from the state of Missouri. Reinspect in 90 days
|
8/29/2024
|