Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The unintended motion testing shall be performed before the inspection is completed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 2/7/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) There are a number of Braille floor indicating tags missing on multiple floors and shall be reinstalled for proper floor identification. 7/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 90 days of inspection. Reinspection is required. 2/7/0202
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri.